Forcing By Using Pcm600 - ABB Relion 670 Series REL670 Commissioning Manual

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 9
Testing IED operation
9.8.3.2
80
IEC15000020 V1 EN
Figure 13:
Example of LHMI menu using BIM3
The signal "freezes" and will not change value even if, for example, a binary input
signal voltage changes level, or if a binary output is activated as the result of a
protection function block activating.

Forcing by using PCM600

In PCM600 the concept is a bit different compared to LHMI. The forcing is
accomplished by entering a forcing session. Within such a session, multiple signals on
multiple I/O boards may be edited and changed at the same time and has no effect on
the IED. Once the user is satisfied with the forcing setup, then all the changes can be
effectuated simultaneously towards the IED, potentially changing inputs and outputs
on multiple I/O boards at the same time. It is also possible to abort this operation
(described in step 6 below) and to
1.
Right click on the IED in the plant structure and select Signal Monitoring.
2.
Click on the List View tab.
3.
Click Forcing Session in the menu IED/Start Forcing.
IEC15000023 V1 EN
4.
Click Start editing signal value for forcing on the tool bar.
IEC15000024 V1 EN
undo all
forcing.
Line distance protection REL670 2.1 IEC
1MRK 506 355-UEN A
Commissioning manual