ABB Relion 670 Series REL670 Commissioning Manual page 97

Line distance protection 2.1 iec
Table of Contents

Advertisement

1MRK 506 355-UEN A
Line distance protection REL670 2.1 IEC
Commissioning manual
Testing functionality by secondary injection
The solid lines designate the diagram applicable when the load current
compensation is active. The solid line and all test points except 13 are
valid for this case.
When the load current compensation is inactive, the dotted lines and
test point 13 are valid. Test points 5, 6, and 7 are not valid for this
measurement.
11
X1
10
40% of RLdFw
80% of RLdFw
IEC05000368 V3 EN
Figure 14:
Distance protection characteristic with test points for phase-to-phase
measurements
Table 17:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPP x tan (ArgRLd)
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
Table continues on next page
X
2
1
80%
3
50%
4
12
120°
a
5
6
R (Ohm/phase)
7
13
9
c
20°
8
0.5 x RFPP
IEC05000368-3-en
set
set
set
set
+ RFPP/2
set
set
+ RFPP/2
set
Section 10
Comments
ArgLd = angle for the maximal load
transfer
91