ABB Relion 670 Series REL670 Commissioning Manual page 187

Line distance protection 2.1 iec
Table of Contents

Advertisement

1MRK 506 355-UEN A
Line distance protection REL670 2.1 IEC
Commissioning manual
Testing functionality by secondary injection
Test for fast fault clearing
Connect the test set for the injection of three phase voltages and currents to the
appropriate terminals of the IED.
Enable the fast fault clearance by setting FastOperation to TRUE, and also
connect the inputs BLKDLFLT to TRUE and FUSEFAIL to FALSE.
Also assume circuit breaker is in closed position, that is CBCLOSED is high, prior
to fault occurrence.
Create a single phase fault on phase L1 such that phase L1 voltage is lower than
UPhSel< times quadrature phase to phase voltage and set Tau to default value.
Activate carrier receive CR signal.
Check that TRIP, TRL1, ARST and ARSTL1 are generated with the conditions
described.
Check that activated trip signals and start signals are blocked by enabling BLKTR
and BLKST.
Check that all activated signals are disabled by BLOCK input.
If required, perform creating faults on the remaining phases in the similar way.
Test of delayed fault clearing for single pole tripping
Connect the test set for the injection of three phase voltages and currents to the
appropriate terminals of the IED.
Enable the delayed fault clearance for single pole tripping by setting Del1phOp to
1Ph (On), Del3PhOp to FALSE (Off) and also connect the inputs BLKDLFLT and
FUSEFAIL to FALSE.
Also assume circuit breaker is in closed position, that is input CBCLD is high,
prior to fault occurrence.
Create a single phase fault on phase L1 such that phase L1 voltage is lower than
UPhSel< times quadrature phase to phase voltage and set Tau to default value and
also inject the residual current such that it exceeds set IN> value.
Check that output TRIN is activated after a set delay of tResCurr if ResCurrOper
is set to high.
Check that TRIP and TRL1 are generated with the conditions described after a
set delay time of t1Ph and the outputs ARST and ARSTL1 are also activated. .
Check that activated trip signals and start signals are blocked by enabling BLKTR
and BLKST.
Check that all activated signals are disabled by BLOCK input.
If required, perform creating faults on the remaining phases in the similar way.
Test of delayed fault clearing for three pole tripping
Connect the test set for the injection of three phase voltages and currents to the
appropriate terminals of the IED.
Enable the delayed fault clearance for three pole tripping by setting Del3phOp to
TRUE (On), Del1PhOp to 3Ph (Off) and also connect the inputs BLKDLFLT and
FUSEFAIL to FALSE.
Also assume circuit breaker is in closed position, that is, the input CBCLOSED is
high prior to fault occurrence.
Section 10
181

Advertisement

Table of Contents
loading

Table of Contents