Section 10
Testing functionality by secondary injection
114
Test point
Reach
Set value
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPP
Table
29
is used in conjunction with figure 26.
11
X1+XN
10
40% of RLdFw
80% of RLdFw
alt. 80% of
RFPE (Load
encroachment)
IEC05000369 V3 EN
Figure 27:
Distance protection characteristic with test points for phase-to-earth
measurements
Table
30
is used in conjunction with figure 27.
set
set
set
set
set
set
X
2
1
80%
3
50%
4
12
5
120°
a
6
R (Ohm/loop)
7
13
9
20°
8
RFPE
IEC05000369-3-en.vsd
1MRK 506 355-UEN A
Comments
Exact: 0.8 x RFPP/2 (ArgDir=20°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Line distance protection REL670 2.1 IEC
Commissioning manual