ABB Relion 670 Series REL670 Commissioning Manual page 120

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
114
Test point
Reach
Set value
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPP
Table
29
is used in conjunction with figure 26.
11
X1+XN
10
40% of RLdFw
80% of RLdFw
alt. 80% of
RFPE (Load
encroachment)
IEC05000369 V3 EN
Figure 27:
Distance protection characteristic with test points for phase-to-earth
measurements
Table
30
is used in conjunction with figure 27.
set
set
set
set
set
set
X
2
1
80%
3
50%
4
12
5
120°
a
6
R (Ohm/loop)
7
13
9
20°
8
RFPE
IEC05000369-3-en.vsd
1MRK 506 355-UEN A
Comments
Exact: 0.8 x RFPP/2 (ArgDir=20°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Line distance protection REL670 2.1 IEC
Commissioning manual