Completing The Test; Frequency Protection; Underfrequency Protection Saptuf; Verifying The Settings - ABB Relion 670 Series REL670 Commissioning Manual

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
10.6.7.2
10.7
10.7.1
10.7.1.1
182
Create a L2L3 fault such that their phase voltage magnitudes are lower than
UPhSel< times corresponding quadrature phase to phase voltage and set Tau to
default value.
Check that TRIP, TRL1, TRL2 and TRL3 are generated after the set delay time
of t3Ph and ARST, ARST3PH, ARSTL1, ARSTL2 and ARSTL3 are also
activated.
Check that activated trip signals and start signals are blocked by enabling BLKTR
and BLKST.
Check that all activated signals are disabled by BLOCK input.

Completing the test

Continue to test another function or end the testing by setting the parameter TestMode
to Off under: Main menu/Tests/IED test mode/TESTMODE:1
Restore connections and settings to their original values if they were changed for
testing purposes.

Frequency protection

Underfrequency protection SAPTUF

Prepare the IED for verification of settings outlined in section
verify
settings".

Verifying the settings

Verification of START value and time delay to operate
1.
Check that the IED settings are appropriate, for example the START value and
the time delay.
2.
Supply the IED with three-phase voltages at their rated values.
3.
Slowly decrease the frequency of the applied voltage, until the START signal
appears.
4.
Note the operate value and compare it with the set value.
5.
Increase the frequency until rated operating levels are reached.
6.
Check that the START signal resets.
7.
Instantaneously decrease the frequency of the applied voltage to a value about
1% lower than the operate value (a step change more than 2% will increase the
time delay).
8.
Measure the time delay of the TRIP signal, and compare it with the set value.
Note that the measured time consists of the set value for time delay plus
minimum operate time of the start function (80 - 90 ms).
1MRK 506 355-UEN A
"Preparing the IED to
Line distance protection REL670 2.1 IEC
Commissioning manual

Advertisement

Table of Contents
loading

Table of Contents