ABB Relion 670 Series REL670 Commissioning Manual page 102

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
96
Test point
Reach
Value
5
X
RFFwPE·tan (ArgLd)
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
Table
19
is used together with figure 16.
4
X1
50% RLdFw
IEC09000735 V3 EN
Figure 17:
Operating characteristic for phase selection function, forward
direction phase-to-phase faults
Table 20:
Test points for phase-to-phase loops L1–L2 (Ohm/phase)
Test point
Reach
Value
1
X
X1
R
0
2
X
0
R
RLdFw
R
0,5·RFFwPP
3
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5 RFFwPP
4
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
Table continues on next page
W
(
/
phase
)
X
1
85%
5
ArgNegRes
2
7
6
ArgDir
0.5·RFFwPP
1MRK 506 355-UEN A
Comments
Only when RLdFw < RFFwPE
3
ArgLd
60°
W
(
/
phase
R
IEC09000735-3-en.vsd
Comments
When RLdFw < 0,5·RFFwPP
When RLdFw > 0,5·RFFwPP
R=0.491·X1+0.5 RFFwPP
Can be limited by RFFwPP
Line distance protection REL670 2.1 IEC
Commissioning manual
)