Connection Examples; 2-Wire Start/Stop; Setup Change; Pulse Start/Stop - Danfoss VLT 5000 FLUX Operating Instructions Manual

Hide thumbs Also See for VLT 5000 FLUX:
Table of Contents

Advertisement

Connection examples

2-wire start/stop

Start - Stop (18)
Parameter 302 Start [1]
Quick Stop (27)
Parameter 304 Coasting Stop
inverted [0]
Ramp up Time
Parameter 207/209
[0.01...3600]
Ramp down Time
Parameter 208/210
[0.01...3600]
Quick Stop Ramp
Parameter 212 [0.01...3600]

Pulse start/stop

36
®
VLT
Start (18)
Parameter 302 Pulse Start [2]
Stop (16)
Parameter 300 Stop inverted [2]
Jog
Parameter 305 Jog [5]
Ramp up Time
Parameter 207/209
[0.01...3600]
Ramp down
Parameter 208/210
Time
[0.01...3600]
Jog Speed
Parameter 213 [0.0...Parameter
202]
Jog Ramp Time
Parameter 211 [0.01... 3600]
Quick Stop (27)
Parameter 304 Coasting Stop
inverted [0]

Setup change

Start - Stop (18)
Parameter 302 Start [1]
Active Set-up
Parameter 004 Multi-setup [5]
Set-up MSB
Parameter 306 [11]
Set-up LSB
Parameter 307 [11]
Term 33
Select setup 1
Select setup 2
Select setup 3
Select setup 4
Digital speed up/down
MG.55.A6.02 - VLT is a registered Danfoss trademark
5000 FLUX
Term 32
0
0
1
0
0
1
1
1

Hide quick links:

Advertisement

Table of Contents
loading