Non Ul Compliance - Danfoss VLT 5000 FLUX Operating Instructions Manual

Hide thumbs Also See for VLT 5000 FLUX:
Table of Contents

Advertisement

* Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, with rating plugs listed below
can be used to meet UL-requirements:
5122
rating plug No.
5152
rating plug No.
5202
rating plug No.
5252
rating plug No.
5302
rating plug No.
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.

Non UL compliance

If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027
VLT 5001-5062
VLT 5032-5052
VLT 5072-5500
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
(symmetrical), 500/600 V maximum.
rms
154
SRPK800 A 300
SRPK800 A 400
SRPK800 A 400
SRPK800 A 500
SRPK800 A 600
200-240 V
380-500 V
200-240 V
380-500 V
®
VLT
5000 FLUX
type gG
type gG
type gR
type gR
MG.55.A6.02 - VLT is a registered Danfoss trademark