Indicates the brake power transmitted to an external
brake resistor. The mean power is calculated on
an ongoing basis for the latest 120 sec.

Brake power/sec., parameter 536:

Indicates the given brake power transmitted
to an external brake resistor. Stated as an
instantaneous value.

Heat sink temperature, parameter 537:

States the given heat sink temperature of the
frequency converter. The cut-out limit is 90 ± 5°C,
while the unit cuts back in at 60 ± 5°C.

Alarm word, parameter 538:

States in Hex format whether there is an alarm
on the frequency converter.See section Warning
word 1, Extended status word and Alarm word
for further information.

VLT control word, parameter 539:

Gives the control word sent via the serial communication
port in Hex code to the frequency converter. See
the Design Guide for further information.
Warning word, 1, parameter 540:
States in Hex format whether there is a warning
on the frequency converter. See section Warning
word 1, Extended status word and Alarm word
for further information.
Extended status word Hex, parameter 541:
States in Hex format whether there is a warning
on the frequency converter.
See section Warning word 1, Extended status word
and Alarm word for further information.
Motor RPM, parameter 557:
The displayed value corresponds to the
actual motor RPM.
Motor RPM x scaling, parameter 558:
The displayed value corresponds to the actual
motor RPM multiplied by a factor (scaling)
set in parameter 008.
= factory setting. () = display text [] = value for use in communication via serial communication port