Language; Local/Remote Control; Local Reference; Active Setup - Danfoss VLT 5000 FLUX Operating Instructions Manual

Hide thumbs Also See for VLT 5000 FLUX:
Table of Contents

Advertisement

001 Language

(LANGUAGE)
Value:
English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
Function:
This parameter defines the language to be
used on the display.

002 Local/remote control

(OPERATION SITE)
Value:
Remote control (REMOTE)
Local control (LOCAL)
Function:
There is a choice of two methods of controlling
the frequency converter.
Description of choice:
If Remote control [0] is selected, the frequency
converter can be controlled via:
1. The control terminals or the serial
communication port.
2. The [START] key. However, this cannot overrule
Stop commands (also start-disable) entered via the
digital inputs or the serial communication port.
3. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameter 014, 015 and 017).
If Local control [1] is selected, the frequency
converter can be controlled via:
1. The [START] key. However, this cannot override
Stop commands on the digital terminals (if [4]
has been selected in parameter 013).
2. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameter 014, 015 and 017).
3. The [FWD/REV] key, provided that this has been
activated in parameter 016 and that in parameter
013 a choice of [3] has been made.
4. Via parameter 003 the local reference can
be controlled by means of the "Arrow up"
and "Arrow down" keys.
5. An external control command that can be
connected to terminal 16, 17, 19, 27, 29, 32 or 33.
However, [4] must be selected in parameter 013.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
VLT
NB!:
Please be aware that terminal 37 (hardware
coast) is always active.
[0]
See also section Shift between local and remote control .
[1]
[2]
[3]

003 Local reference

[4]
(LOCAL REFERENCE)
[5]
Value:
Parameter 203 = [0] set for:
Ref
- Ref
MIN
MAX
Parameter 203 = [1] set for:
-Ref
- + Ref
MAX
Function:
This parameter allows manual setting of the
[0]
desired reference value.
[1]
The unit follows the configuration selected in
parameter 100, where Speed is measured in
RPM, and torque in NM.
Description of choice:
Local [1] must be selected in parameter 002
for this parameter to be used.
The set value is saved in the case of a voltage
drop-out, see parameter 019.
In this parameter Data Change Mode is not exited
automatically (after time out).
Local reference cannot be set via the serial
communication port.
Warning: Since the value set is stored
after the power has been cut, the motor
may start without warning when the
power is reapplied; if parameter 019 is changed
to Auto restart, use saved ref. [0].

004 Active Setup

(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
Setup 2 (SETUP 2)
Setup 3 (SETUP 3)
Setup 4 (SETUP 4)
MultiSetup (MULTI SETUP)
®
5000 FLUX
MAX
000.000
000.000
[0]
[1]
[2]
[3]
[4]
[5]