value to be changed will flash. To accept the new
setting, press [OK], to abort, press [CANCEL].
Initialisation to factory setting
The frequency converter can be initialised to
factory settings in two ways.
Initialisation by parameter 620
- Recommended initialisation
•
Select parameter 620
•
Press [CHANGE]
•
Select "Initialisation"
•
Press the [OK] key
•
Cut off the mains supply and wait until
the display turns off.
•
Reconnect the mains supply - the frequency
converter is now reset.
This parameter initialises all except:
500
Serial communication address
501
Baud rate for serial communication
601-605
Operating data
615-617
Fault logs
Manual initialisation
•
Disconnect from mains and wait until the
display turns off.
•
Press the following keys at the same time:
[Display/status]
[Change data]
[OK]
•
Reconnecting the mains supply while
pressing the keys.
•
Release the keys
•
The frequency converter has now been
programmed for the factory setting.
This parameter initialises all except:
600-605
Operating data
NB!:
Settings for serial communication and
fault logs are reset.
50
®
VLT
5000 FLUX
MG.55.A6.02 - VLT is a registered Danfoss trademark
Need help?
Do you have a question about the VLT 5000 FLUX and is the answer not in the manual?
Questions and answers