Hours Run, Parameter 601; Kwh Counter, Parameter 602: - Danfoss VLT 5000 FLUX Operating Instructions Manual

Hide thumbs Also See for VLT 5000 FLUX:
Table of Contents

Advertisement

Parameter no.
Operating data
600
Operating hours
601
Hours run
602
kWh counter
603
No. of cut-ins
604
No. of overtemps
605
No. of overvoltages
Function:
These parameters can be read out via the
serial communication port and via the display
in the parameters.
Description of choice:
Operating hours, parameter 600:
Indicates the number of hours in which the frequency
converter has been in operation.
The value is updated in the frequency converter every
hour and saved when the unit is turned off.

Hours run, parameter 601:

Indicates the number of hours in which the
frequency converter has been in operation since
reset in parameter 619.
The value is updated in the frequency converter every
hour and saved when the unit is turned off.
Parameter
Description
no.
Data log
606
Digital inputs
607
Control word
608
Status word
609
Reference
611
Output frequency
612
Output voltage
613
Output current
614
DC link voltage
Function:
Via this parameter it is possible to see up to 20
data-logs, where [0] is the latest log and [19] the
oldest. Each data-log is made every 160 ms as long
as a start signal has been given. If a stop signal is
given, the latest 20 data-logs will be saved and the
values will be available on the display. This is useful,
e.g. when carrying out service after a trip.
This parameter can be read out via the serial
communication port or via the display.
Description of choice:
The data-log number is stated in square brackets: [1].
Data-logs are frozen if there is a trip and released when
the frequency converter is subsequently reset.
Data-logging is active while the motor is running.
= factory setting. () = display text [] = value for use in communication via serial communication port
116
Description
(OPERATING
HOURS)
(RUNNING HOURS)
(KWH COUNTER)
(POWER UP's)
(OVER TEMP's)
(OVER VOLT'S)
Display text
(LOG: DIGITAL INP)
(LOG: CONTROL WORD
(LOG: BUS STAT WD)
(LOG: REFERENCE)
(LOG: MOTOR FREQ.)
(LOG: MOTOR VOLT)
(LOG: MOTOR CURR.)
(LOG: DC LINK VOLT)
VLT
Display text
Hours
Hours

kWh counter, parameter 602:

States the power consumption from mains in
kWh as a mean value over one hour. Reset
counter: Parameter 618.
No. of cut-ins, parameter 603:
States the number of power-ups of the supply
voltage to the frequency converter.
No. of overtemps, parameter 604:
States the number of temperature faults there has
been on the frequency converter.
No. of overvoltages, parameter 605:
States the number of overvoltages there has
been on the frequency converter.
Decimal
Decimal
Decimal
Digital inputs, parameter 606:
The value for the digital inputs is given as a decimal
figure within the range of 0-255.
The data-log number is stated in square brackets: [1]
EXT. REFERENCE, %
63.0 %
606 DATALOG:DIGITALINPUT
[0] 40
Control word, parameter 607:
The value for the control word is given as a decimal
figure within the range of 0-65535.
MG.55.A6.02 - VLT is a registered Danfoss trademark
®
5000 FLUX
Unit
Range
0 - 130,000.0
0 - 130,000.0
kWh
0 - 9999
Nos.
0 - 9999
Nos.
0 - 9999
Nos.
0 - 9999
Unit
Range
0 - 255
0 - 65535
0 - 65535
%
0 - 100
Hz.
0.0 - 999.9
Volt
50 - 1000
Amp
0.0 - 999.9
Volt
0.0 - 999.9

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT 5000 FLUX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents

Save PDF