Non-Ul Compliance Fuses - Danfoss VLT HVAC Drive FC 100 Series Design Manual

Hide thumbs Also See for VLT HVAC Drive FC 100 Series:
Table of Contents

Advertisement

How to Install

5.2.9 Non-UL Compliance Fuses

Non-UL Compliance fuses
Adjustable frequency drive
200–240 V - T2
1K1-1K5
2K2
3K0
3K7
5
5
5K5
7K5
11K
15K
18K5
22K
30K
37K
45K
380–480 V - T4
1K1-1K5
2K2-3K0
4K0-5K5
7K5
11K–15K
18K
22K
30K
37K
45K
55K
75K
90K
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Table 5.10 Non-UL Fuses 200V to 480V
If UL/cUL is not to be complied with, Danfoss recommends using the following fuses, which will ensure compliance with
EN50178:
Adjustable Frequency Drive
P110 - P250
P315 - P450
Table 5.11 Compliance with EN50178
5-16
®
VLT
HVAC Drive Design Guide
Max. fuse size
1
16A
1
25A
25A
1
1
35A
1
50A
63A
1
63A
1
1
80A
1
125A
125A
1
1
160A
1
200A
250A
1
1
10A
1
16A
25A
1
1
35A
1
63A
1
63A
63A
1
1
80A
1
100A
125A
1
160A
1
1
250A
1
250A
Voltage (V)
380–480
380–480
MG11BB22 - VLT
®
is a registered Danfoss trademark
Voltage (V)
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type gG
200–240
type aR
200–240
type aR
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type gG
380–500
type aR
380–500
type aR
Type
type gG
type gR
Type

Advertisement