Iec 61850 Goose Integers; Remaining Connection Status - GE C70 Instruction Manual

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

6 ACTUAL VALUES

PATH: ACTUAL VALUES
STATUS
 IEC 61850
 GOOSE UINTEGERS
MESSAGE
MESSAGE
The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica-
tions capability. This feature is specified as a software option at the time of ordering. See the Order Codes
section in chapter 2 for details.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
PATH: ACTUAL VALUES
STATUS
 COMM STATUS
 REMAINING CONNECT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These values specify the remaining number of TCP connections still available for each protocol. The display depends on
the options applicable to your device, for example the PMU entry does not display when not applicable. Each time a con-
nection is used, the remaining number of connections decrements. When released, the remaining number of connections
increments. If no connection is made over the specific protocol, the number equals the maximum number available for the
specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
— The number of IEC 61850 connections remaining.
MMS TCP
— The maximum number of PMU TCP connections matches the number of aggregators. The maximum number
PMU TCP
of aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with
a PMU. The remaining number of aggregators displays here.
GE Multilin

IEC 61850 GOOSE UINTEGERS
UINT INPUT
1
0
UINT INPUT
2
0
UINT INPUT 16
0

COMM STATUS REMAINING CONNECT
MMS TCP(max 5)
5
MODBUS TCP(max 4)
4
DNP TCP (max 2)
2
IEC-104 (max 2)
2
PMU TCP
1
C70 Capacitor Bank Protection and Control System

6.2.16 IEC 61850 GOOSE INTEGERS

6.2.17 REMAINING CONNECTION STATUS

Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
Range: 1 to 4
6.2 STATUS
6
6-9

Advertisement