Time Of Day Timers - GE C70 Instruction Manual

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 TIME OF DAY TIMER 1
The time of day timer function provides the ability to program control actions based on real time. There are five identical
time of day timers, each with an independent start and stop time setting. Each timer is on when the C70 real-time clock/cal-
endar value is later than its programmed start time, and earlier than its programmed stop time. The timers wrap around
24 h as illustrated below.
5
The
TIME OF DAY 1 ON
the
TIME OF DAY 1 START
the figure below). These operands can be combined in FlexLogic with the day and month FlexLogic operands and/or with
FlexElements operating on the
any time and date condition for custom time or season-based control actions. To activate these FlexAnalog parameters,
enable at least one time of day timer.
Figure 5–96: CLOSE/OPEN/MAINTAIN CONTROL VIA FLEXLOGIC OPERANDS
If the relay is connected to an external clock that follows daylight time changes, care should be taken that the changes do
not result in undesired operation. The following settings are available for each time of day timer element.
TIME OF DAY TIMER 1 START: This setting is used to program the relay clock/calendar value for which the timer turns
on.
TIME OF DAY TIMER 1 STOP: This setting is used to program the relay clock/calendar value for which the timer turns
off.
TIME OF DAY TIMER 1 EVENTS: If enabled, the
logged.
5-216


TIME OF DAY TIMERS

TIME OF DAY TIMER 1
FUNCTION: Disabled
TIME OF DAY TIMER 1
MESSAGE
START TIME: 00:00
TIME OF DAY TIMER 1
MESSAGE
STOP TIME: 23:59
TIME OF DAY TIMER 1
MESSAGE
TARGETS: Disabled
TIME OF DAY TIMER 1
MESSAGE
EVENTS: Disabled
Figure 5–95: TIME OF DAY TIMER EXAMPLE
FlexLogic operand follows the state of the timers. In addition, one-second pulses are generated on
and
FlexLogic operands when the timers turn on and off, respectively (see
TIME OF DAY 1 STOP
,
DAYOFYEAR
DAYOFMONTH
TIME OF DAY TIMER 1 ON
TIME OF DAY TIMER 1 START
TIME OF DAY TIMER 1 STOP
C70 Capacitor Bank Protection and Control System
TIME OF DAY TIMER 1(5)
Range: Disabled, Enabled
Range: 00:00 to 23:59 in steps of 00:01
Range: 00:00 to 23:59 in steps of 00:01
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
t start (5)
t stop (5)
, and
FlexAnalog parameters to create virtually
SECONDOFDAY
Start time
Stop time
842801A1.CDR
and
TIME OF DAY TIMER 1 ON
5 SETTINGS
5.7.5 TIME OF DAY TIMERS
Time of day timer 1
Time of day timer 2
Time of day timer 3
Time of day timer 4
Time of day timer 5
842800A1.CDR
events are
TIME OF DAY TIMER 1 OFF