GE C70 Instruction Manual page 318

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
g) BANK VOLTAGE DIFFERENTIAL (ANSI 87V, IEC PDIF)

PATH: SETTINGS
GROUPED ELEMENTS
 VOLTAGE
 DIFFERENTIAL 1
5
5-194
SETTING GROUP 1(6)
VOLTAGE DIF 1
FUNCTION: Disabled
VOLTAGE DIF 1 BUS
MESSAGE
SOURCE: SRC 1
VOLTAGE DIF 1 TAP
MESSAGE
SOURCE: SRC 1
VOLTAGE DIF 1 BANK
MESSAGE
GROUND: Grounded
VOLTAGE DIF 1 MATCH
MESSAGE
FACTOR A:
VOLTAGE DIF 1 MATCH
MESSAGE
FACTOR B:
VOLTAGE DIF 1 MATCH
MESSAGE
FACTOR C:
VOLTAGE DIF 1 STG 1A
MESSAGE
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2A
MESSAGE
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3A
MESSAGE
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4A
MESSAGE
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1B
MESSAGE
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2B
MESSAGE
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3B
MESSAGE
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4B
MESSAGE
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1C
MESSAGE
PICKUP: 0.010 pu
VOLTAGE DIF 1 STG 2C
MESSAGE
PICKUP: 0.020 pu
VOLTAGE DIF 1 STG 3C
MESSAGE
PICKUP: 0.030 pu
VOLTAGE DIF 1 STG 4C
MESSAGE
PICKUP: 0.040 pu
VOLTAGE DIF 1 STG 1
MESSAGE
PKP DELAY: 30.00 s
VOLTAGE DIF 1 STG 2
MESSAGE
PKP DELAY: 10.00 s
C70 Capacitor Bank Protection and Control System

VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Grounded, Ungrounded
Range: 0.5000 to 2000.0000 in steps of 0.0001
2.0000
Range: 0.5000 to 2000.0000 in steps of 0.0001
2.0000
Range: 0.5000 to 2000.0000 in steps of 0.0001
2.0000
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.001 to 1.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
5 SETTINGS

VOLTAGE DIFFERENTIAL 1(3)