6 ACTUAL VALUES
Voltage harmonics are calculated only for Wye connected phase VTs. Ensure the
VOLTAGE BANK F5
NOTE
PATH: ACTUAL VALUES
METERING
CAPACITOR CONTROL
MESSAGE
MESSAGE
MESSAGE
These values indicate the time remaining before the next permissible close operation for each of the four capacitor banks.
a) MAIN MENU
PATH: ACTUAL VALUES
METERING
CAPACITOR BANK
MESSAGE
MESSAGE
MESSAGE
The capacitor bank menu contains the actual values for the voltage differenital, neutral voltage unbalance, phase current
unbalance, and neutral current unbalance elements.
b) VOLTAGE DIFFERENTIAL
PATH: ACTUAL VALUES
METERING
VOLTAGE
DIFFERENTIAL 1
MESSAGE
MESSAGE
These actual values display the bus and differential signals in per-unit values of the nominal bus voltage for phases A, B,
and C.
c) NEUTRAL VOLTAGE UNBALANCE
PATH: ACTUAL VALUES
METERING
NEUTRAL VOLTAGE
UNBALANCE 1
GE Multilin
setting is "Wye" to enable voltage harmonics metering.
PHASE VT XX CONNECTION
CAPACITOR CONTROL
CAP 1 DISCHARGE TIME:
0 s
CAP 2 DISCHARGE TIME:
0 s
CAP 3 DISCHARGE TIME:
0 s
CAP 4 DISCHARGE TIME:
0 s
CAPACITOR BANK
VOLTAGE
DIFFERENTIAL
NEUTRAL VOLTAGE
UNBALANCE
PHASE CURRENT
UNBALANCE
NEUTRAL CURRENT
UNBALANCE
CAPACITOR BANK
Bus Va:
0.0000 pu
Dif Va:
0.0000 pu
Bus Vb:
0.0000 pu
Dif Vb:
0.0000 pu
Bus Vc:
0.0000 pu
Dif Vc:
0.0000 pu
CAPACITOR BANK
NEUTRAL-POINT Vx:
0.0000 pu / 0.0°
C70 Capacitor Bank Protection and Control System
SYSTEM SETUP
See page 6-3.
See page 6-19.
See page 6-3.
See page 6-4.
VOLTAGE DIFFERENTIAL
VOLTAGE DIFFERENTIAL 1(3)
NEUTRAL VOLTAGE...
NEUTRAL VOLTAGE UNBALANCE 1(3)
6.3 METERING
AC INPUTS
6.3.3 CAPACITOR CONTROL
6.3.4 CAPACITOR BANK
6-19
6