Iec 61850 Goose Integers - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.8 INPUTS AND OUTPUTS
Table 5–23: GOOSE ANALOG INPUT BASE UNITS (Sheet 2 of 2)
ELEMENT
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
The GOOSE analog input FlexAnalog values are available for use in other N60 functions that use FlexAnalog values.

PATH: SETTINGS
INPUTS/OUTPUTS
 GOOSE UINTEGER
 INPUT 1
5
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE
number.
UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is "Last Known", the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
"Default Value", then the value of the GOOSE uinteger input is defined by the
The GOOSE integer input FlexInteger values are available for use in other N60 functions that use FlexInteger values.
5-242
BASE UNITS
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE

IEC 61850 GOOSE UINTEGERS
UINTEGER
1000
UINTEGER
MESSAGE
MODE: Default Value
is set to "Default Value".This setting is stored as a 32-bit unsigned integer
N60 Network Stability and Synchrophasor Measurement System
 I
for the +IN and –IN inputs
BASE
BASE

5.8.15 IEC 61850 GOOSE INTEGERS


GOOSE UINTEGER INPUT 1(16)
Range: 0 to 429496295 in steps of 1
1 DEFAULT:
Range: Default Value, Last Known
1 DEFAULT
UINTEGER 1 DEFAULT
5 SETTINGS
setting.
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents