5.8 INPUTS AND OUTPUTS
5 SETTINGS
b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES
In a C70 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the


SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL


setting.
GSSE/GOOSE CONFIGURATION
TRANSMISSION
FIXED GOOSE
GOOSE ID
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the


SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE


setting.
CONFIGURATION
TRANSMISSION
GSSE
GSSE ID
In C70 releases previous to 5.0x, these name strings were represented by the
setting.
RELAY NAME