Advertisement

5.5 FLEXLOGIC
Table 5–15: C70 FLEXLOGIC OPERANDS (Sheet 7 of 10)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
SELECTOR 1 POS Y
Selector switch
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 2
ELEMENT:
SETTING GROUP ACT 1
Setting group
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
ELEMENT:
SRC1 50DD OP
Disturbance
SRC2 50DD OP
detector
SRC3 50DD OP
SRC4 50DD OP
SRC5 50DD OP
SRC6 50DD OP
ELEMENT:
SRC1 VT FF OP
VTFF (Voltage
SRC1 VT FF DPO
transformer fuse
SRC1 VT FF VOL LOSS
failure)
5
SRC1 VT NEU WIRE OPEN
SRC2 VT FUSE FAIL to SRC6
ELEMENT:
SWITCH 1 OFF CMD
Disconnect switch
SWITCH 1 ON CMD
SWITCH 1 CLOSED
SWITCH 1 OPEN
SWITCH 1 DISCREP
SWITCH 1 TROUBLE
SWITCH 1 ΦA CLSD
SWITCH 1 ΦA OPEN
SWITCH 1 ΦA BAD ST
SWITCH 1 ΦA INTERM
SWITCH 1 ΦB CLSD
SWITCH 1 ΦB OPEN
SWITCH 1 ΦB BAD ST
SWITCH 1 ΦB INTERM
SWITCH 1 ΦC CLSD
SWITCH 1 ΦC OPEN
SWITCH 1 ΦC BAD ST
SWITCH 1 ΦC INTERM
SWITCH 1 BAD STATUS
SWITCH 2 to 24
ELEMENT:
THERMAL PROT 1 PKP
Thermal overload
THERMAL PROT 1 OP
protection
THERMAL PROT 2
ELEMENT:
TIME OF DAY 1 OFF
Time of day timer
TIME OF DAY 1 ON
TIME OF DAY 1 START
TIME OF DAY 1 STOP
TIME OF DAY 2 to 5
5-126
OPERAND DESCRIPTION
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
Same set of operands as shown above for SELECTOR 1
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
Source 5 disturbance detector has operated
Source 6 disturbance detector has operated
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 10% and V1 below 5%
of nominal)
Source 1 VT neutral wire open detected.When the VT is connected in Delta,
this function should not be enabled because there is no neutral wire for Delta
connected VT.
Same set of operands as shown for SRC1 VT FUSE FAIL
Disconnect switch 1 open command initiated
Disconnect switch 1 close command initiated
Disconnect switch 1 is closed
Disconnect switch 1 is open
Disconnect switch 1 has discrepancy
Disconnect switch 1 trouble alarm
Disconnect switch 1 phase A is closed
Disconnect switch 1 phase A is open
Disconnect switch 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase B is closed
Disconnect switch 1 phase B is open
Disconnect switch 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase B intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase C is closed
Disconnect switch 1 phase C is open
Disconnect switch 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase C intermediate status is detected (transition from
one position to another)
Disconnect switch 1 bad status is detected on any pole
Same set of operands as shown for SWITCH 1
Thermal overload protection 1 picked up
Thermal overload protection 1 operated
Same set of operands as shown for THERMAL PROT 1
Time of day timer 1 is off
Time of day timer 1 is on
One-second pulse at set time of day timer 1 start time
One-second pulse at set time of day timer 1 stop time
Same set of operands as shown for TIME OF DAY 1
C70 Capacitor Bank Protection and Control System
5 SETTINGS