5.6 GROUPED ELEMENTS
NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon
NEG SEQ DIR OC1 TYPE
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
5
Figure 5–76: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC
5-186
selection, this pickup threshold applies to zero- or negative-sequence current. When
selection, this pickup threshold applies to zero- or negative-sequence current. When
C70 Capacitor Bank Protection and Control System
5 SETTINGS