GE C70 Instruction Manual page 160

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the
tings.
Table 5–6: PORT AND PROTOCOL COMBINATIONS
PROTOCOL
DNP CHANNEL 1(2) PORT
SETTING
SETTINGS
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Channel 1: Eth TCP
Channel 2: none
Channel 1: none
Channel 2: Eth TCP
Channel 1: Eth UDP
Channel 2: none
Channel 1: Eth TCP
Channel 2: RS485
Channel 1: Eth TCP
Channel 2: RS232
Channel 1: Eth UDP
Channel 2: RS485
Channel 1: Eth UDP
Channel 2: RS232
Channel 1: RS485
Channel 2: Eth TCP
Channel 1: RS232
Channel 2: Eth TCP
5
Channel 1: RS485
Channel 2: RS232
Channel 1: RS232
Channel 2: RS485
Channel 1: RS485
Channel 2: none
IEC 104
IEC 103
j) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 DNP PROTOCOL
5-36
RS232
Modbus
Modbus
Modbus
Modbus
Modbus
DNP
Modbus
DNP
Modbus
DNP
DNP
DNP
Modbus
Modbus
Modbus

COMMUNICATIONS
 DNP CHANNELS
DNP ADDRESS:
MESSAGE
1
 DNP NETWORK
MESSAGE
 CLIENT ADDRESSES
DNP TCP/UDP PORT
MESSAGE
NUMBER: 20000
DNP UNSOL RESPONSE
MESSAGE
FUNCTION: Disabled
DNP UNSOL RESPONSE
MESSAGE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MESSAGE
MAX RETRIES: 10
DNP UNSOL RESPONSE
MESSAGE
DEST ADDRESS: 1
C70 Capacitor Bank Protection and Control System
PROTOCOL
RS485
ETHERNET
Modbus
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
DNP, Modbus, IEC 61850
Modbus
DNP, Modbus, IEC 61850
DNP
Modbus, IEC 61850
DNP
Modbus, IEC 61850
DNP
Modbus, IEC 61850
Modbus
IEC 104, Modbus, IEC 61850
IEC 103
Modbus, IEC 61850

DNP PROTOCOL
Range: see sub-menu below
Range: 0 to 65519 in steps of 1
Range: see sub-menu below
Range: 0 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 60 s in steps of 1
Range: 1 to 255 in steps of 1
Range: 0 to 65519 in steps of 1
5 SETTINGS