GE C70 Instruction Manual page 153

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5 SETTINGS
Multiple LANS, No Redundancy
The following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) is
connected, access to the public network on LAN2, to which port 2 (P2) is connected and communications with SCADA on
LAN3, to which port 3 (P3) is connected. There is no redundancy.
EnerVista Software
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the rout-
ing settings.
To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating
information, such as the serial number and order code of your device.
PATH: SETTINGS
PRODUCT SETUP
 NETWORK PORT 1
MESSAGE
MESSAGE
GE Multilin
Figure 5–6: MULTIPLE LANS, NO REDUNDANCY
Public Network
LAN1
LAN2
ML3000
ML3000
P1
P2
IP1/
IP2/
MAC2
MAC1
UR


COMMUNICATIONS
NETWORK 1(3)
PRT1 IP ADDRESS:
127.0.0.1
PRT1 SUBNET IP MASK:
255.0.0.0
PRT1 GOOSE ENABLED:
Enabled
C70 Capacitor Bank Protection and Control System
SCADA
LAN3
ML3000
P3
IP3/
MAC3
859710A2.vsd
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Enabled, Disabled
5.2 PRODUCT SETUP
5
5-29