APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 21 of 65)
ADDR
REGISTER NAME
Passwords (Read/Write Setting)
402A
Command Password Access Timeout
402B
Setting Password Access Timeout
402C
Invalid Password Attempts (before lockout)
402D
Password Lockout Duration
Passwords (Read/Write)
402E
Password Access Events
Passwords (Read/Write Setting)
402F
Local Setting Auth
4031
Remote Setting Auth
4033
Access Auth Timeout
User Display Invoke (Read/Write Setting)
4040
Invoke and Scroll Through User Display Menu Operand
LED Test (Read/Write Setting)
4048
LED Test Function
4049
LED Test Control
Preferences (Read/Write Setting)
404F
Language
4050
Flash Message Time
4051
Default Message Timeout
4052
Default Message Intensity
4053
Screen Saver Feature
4054
Screen Saver Wait Time
4055
Current Cutoff Level
4056
Voltage Cutoff Level
Communications (Read/Write Setting)
407D
COM2 Selection
407E
COM1 Minimum Response Time
407F
COM2 Minimum Response Time
4080
Modbus Slave Address
4083
RS485 Com1 Baud Rate
4084
RS485 Com1 Parity
4085
RS485 Com2 Baud Rate
4086
RS485 Com2 Parity
4087
Port 1 IP Address
4089
Port 1 IP Subnet Mask
408B
Port 1 Gateway IP Address
408D
Network Address NSAP
4097
Port 1 Link Loss Alert
4098
Port 2 Link Loss Alert
4099
Port 3 Link Loss Alert
409A
DNP Channel 1 Port
409B
DNP Channel 2 Port
409C
DNP Address
409E
DNP Client Addresses (2 items)
40A3
TCP Port Number for the Modbus protocol
40A4
TCP/UDP Port Number for the DNP Protocol
40A5
TCP Port Number for the HTTP (Web Server) Protocol
40A6
Main UDP Port Number for the TFTP Protocol
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means "automatic") (2 items)
40A9
DNP Unsolicited Responses Function
40AA
DNP Unsolicited Responses Timeout
40AB
DNP Unsolicited Responses Maximum Retries
GE Multilin
1 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0.002 to 0.02
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
5 to 480
min
1
5 to 480
min
1
2 to 5
---
1
5 to 60
min
1
0 to 1
---
1
---
1
---
1
5 to 480
min
1
---
1
0 to 1
---
1
---
1
0 to 5
---
1
0.5 to 10
s
0.1
10 to 900
s
1
0 to 3
---
1
0 to 1
---
1
1 to 65535
min
1
pu
0.001
0.1 to 1
V
0.1
0 to 3
---
1
0 to 1000
ms
10
0 to 1000
ms
10
1 to 254
---
1
0 to 11
---
1
0 to 2
---
1
0 to 11
---
1
0 to 2
---
1
---
1
---
1
---
1
---
---
---
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 5
---
1
0 to 65519
---
1
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 1
---
1
0 to 60
s
1
1 to 255
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F001
5
F001
30
F001
3
F001
5
F102
0 (Disabled)
F300
1
F300
1
F001
30
F300
0
F102
0 (Disabled)
F300
0
F531
0 (English)
F001
10
F001
300
F101
0 (25%)
F102
0 (Disabled)
F001
30
F001
20
F001
10
F601
0 (RS485)
F001
0
F001
0
F001
254
F112
8 (115200)
F113
0 (None)
F112
8 (115200)
F113
2 (Even)
F003
2130706433
F003
4278190080
F003
56554497
F074
0
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F177
0 (None)
F177
0 (None)
F001
1
F003
0
F001
502
F001
20000
F001
80
F001
69
F001
0
F102
0 (Disabled)
F001
5
F001
10