GE C70 Instruction Manual page 342

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS
5
5-218
CAP 1 TRIP 4:
MESSAGE
Off
CAP 1 TRIP 5:
MESSAGE
Off
CAP 1 TRIP 6:
MESSAGE
Off
CAP 1 SWITCH TO
MESSAGE
MANUAL ON TRIP: Yes
CAP 1 AUTO CTRL EN:
MESSAGE
Off
CAP 1 MAN CTRL EN:
MESSAGE
Off
CAP 1 REMOTE OPEN:
MESSAGE
Off
CAP 1 LOCAL OPEN:
MESSAGE
Off
CAP 1 AUTO OPEN:
MESSAGE
Off
CAP 1 BKR OPEN 52b:
MESSAGE
Off
CAP 1 TRIP SEAL-IN
MESSAGE
DELAY: 0.400 s
CAP 1 REMOTE CLOSE:
MESSAGE
Off
CAP 1 LOCAL CLOSE:
MESSAGE
Off
CAP 1 AUTO CLOSE:
MESSAGE
Off
CAP 1 BKR CLSD 52a:
MESSAGE
Off
CAP 1 DISCHARGE
MESSAGE
DELAY: 300 s
CAP 1 CLOSE SEAL-IN
MESSAGE
DELAY: 0.400 s
CAP 1 BKR CLOSE BLK:
MESSAGE
Off
CAP 1 CLS OVERRIDE:
MESSAGE
Off
CAP 1 TARGETS:
MESSAGE
Disabled
CAP 1 EVENTS:
MESSAGE
Disabled
C70 Capacitor Bank Protection and Control System
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Yes, No
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.000 to 60.000 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 3600 s in steps of 1
Range: 0.000 to 60.000 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents