2.1 INTRODUCTION
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the C70, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password applies.
Password access events are logged in the Event Recorder.
c) CYBERSENTRY SECURITY
2
CyberSentry Embedded Security is a software option that provides advanced security services. When this option is pur-
chased, the basic password security is disabled automatically.
CyberSentry provides security through the following features:
An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that
is centrally managed, enables user attribution, provides accounting of all user activities, and uses secure standards-
based strong cryptography for authentication and credential protection.
A Role-Based Access Control (RBAC) system that provides a permission model that allows access to UR device oper-
ations and configurations based on specific roles and individual user accounts configured on the AAA server (that is,
Administrator, Supervisor, Engineer, Operator, Observer).
Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM)
systems for centralized cybersecurity monitoring.
Strong encryption of all access and configuration network messages between the EnerVista software and UR devices
using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter
Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the
National Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems.
CYBERSENTRY USER ROLES
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user's logged in
role.
Example: Administrative functions can be segmented away from common operator functions, or engineering type access,
all of which are defined by separate roles, as shown in the following figure, so that access of UR devices by multiple per-
sonnel within a substation is allowed.
The table lists the roles that are supported and their corresponding capabilities.
Table 2–3: PERMISSIONS BY USER ROLE FOR CYBERSENTRY
Roles
Device Definition
Settings
|------------ Product Setup
2-4
Figure 2–2: CYBERSENTRY USER ROLES
Administrator
Complete access
R
C70 Capacitor Bank Protection and Control System
2 PRODUCT DESCRIPTION
Engineer
Operator
Complete access
Command
except for
menu
CyberSentry
Security
R
R
Supervisor
Observer
Authorizes
Default role
writing
R
R