5 SETTINGS
General Security Settings
SETTING NAME
DESCRIPTION
Session Lockout
Number of failed authentications before the
device blocks subsequent authentication
attempts for the lockout period
Session Lockout
The period in minutes that a user is prevented
Period
from logging in after being locked out
Syslog Server IP
The IP address of the target Syslog server to
Address
which all security events are transmitted
Syslog Server Port
The UDP port number of the target syslog server
Number
to which all security events are transmitted
Device
When enabled, local device authentication with
Authentication
roles is allowed. When disabled, the UR only
authenticates to the AAA server (RADIUS).
NOTE: Administrator and Supervisor (if still
enabled) remain active even after device
authentication is disabled. The only permission
for local Administrator is to re-enable device
authentication when device authentication is
disabled. To re-enable device authentication, the
Supervisor unlocks the device for setting
changes, and then the Administrator can re-
enable device authentication.
Firmware Locked
Indicates if the device receives firmware
upgrades. If Yes and the firmware upgrade
attempt is made, the device denies the upgrade
and displays an error message that the lock is
set. On each firmware upgrade, this setting goes
back to the default.
Factory Service
When enabled (checkbox selected), the device
Mode
can go into factory service mode. To enable,
Supervisor authentication is necessary.
Restore to Defaults Sets the device to factory defaults
Supervisor role
When enabled (checkbox selected), the
Supervisor role is active. To enable,
Administrator authentication is necessary. When
disabled, the Supervisor role is inactive. To
disable, Supervisor authentication is necessary.
RADIUS user
Ensure that RADIUS user names are not the
names
same as local/device role names
Password
Local/device roles except for Observer are
password-protected. All RADIUS users are
password-protected.
Security Alarm Settings
SETTING NAME
DESCRIPTION / DETAILS
Failed
A threshold number indicating when an alarm is
Authentications
set off to indicate too many failed authentication
attempts
Firmware lock
A Boolean value indicating if the device can
receive a firmware upgrade. If Yes and a
firmware upgrade attempt is made, the device
alarm activates. If No the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
Settings lock
A Boolean value indicating if the device can
accept any settings changes. If Yes and a
settings change attempt is made, the device
alarm activates. If No, the device alarm does not
activate.
GE Multilin
C70 Capacitor Bank Protection and Control System
MIN
MAX
DEFAULT UNITS MINIMUM
0 (lockout
99
3
disabled)
0 (no period) 9999
3
0.0.0.0
223.255.
0.0.0.0
255.254
1
65535
514
Disabled
Enabled
Enabled
No
Yes
Yes
Disabled
Enabled
Disabled
No
Yes
No
Disabled
Enabled
Enabled
See RADIUS
See
server
RADIUS
documents
server
documents
See the
See the
Change
Password
following
Me1#
Requirement
password
s section
section for
requireme
nts
MIN
MAX
DEFAULT UNITS
0
99
3
(disabled)
No
Yes
Yes
No
Yes
Yes
5.2 PRODUCT SETUP
PERMISSION
-
Administrator
min
Administrator
-
Administrator
-
Administrator
-
Administrator
-
Administrator
-
Supervisor
(Administrator
when Supervisor
is disabled)
-
Administrator
-
Administrator to
enable and
Supervisor to
disable
-
Administrator
Text
The specified role
and Administrator,
except for
Supervisor, where
it is only itself
MINIMUM
PERMISSIONS
-
Administrator
-
Administrator
-
Supervisor
(Administrator if
Supervisor has
been disabled)
5-17
5

Advertisement

Table of Contents
loading

Table of Contents