Wiring (Main Circuit Terminal); Connected Device, Wire Size And Main Circuit Terminal Tightening Torque; Precautions For Using Regenerative Brakes - Panasonic AAD03011 Instruction Manual

Elevator door controller
Table of Contents

Advertisement

Wiring (Main Circuit Terminal)

Power
supply
Circuit breaker
(MCCB)
Note) Always connect protective devices such as fuse for overcurrent, short circuits
and leakage protection to the input terminal.
Connected Device, Wire Size and Main Circuit Terminal
Tightening Torque
Inverter capacity Circuit breaker
0.4 kW
Note1) If the breaker's overcurrent trip is a magnetic type, the device could overheat
due to higher harmonics. Use a load rate of 50% or less in this case.
Note2) When using an installed circuit breaker with motor protection, remove it.

Precautions for Using Regenerative Brakes

1 When using the regenerative brake, select the one with brakes. The brake
resistor is built in the inverter. (It is built in the radiation fin.)
2 When using regenerative brakes, set the parameter P17 data to"0".
The brakes will not activate when the factory setting "1" is set.
3 The regenerative brake specifications are shown below. Carefully consider
the working conditions before using these brakes.
Note that the inverter could be damaged if the specifications are exceeded.
Maximum duty factor (%ED): 2%
Maximum working time: 3s
Maximum torque: 100%
Screw size
Main circuit terminal: M4
Brake resistor
connection
terminal
Class D(3) grounding
BC 30N 10A
Grounding terminal: M4
Main circuit terminals
Ground
terminal
Tightening torque
1.2 N m
Ground marking
Motor
IM
Wire size
2
2 mm
14AWG
17