3.1 Wiring of Terminal Block

3.1.1 Terminal Block, Suitable Wires and Tools

 Supplied terminal block and suitable wires
A screw-down connection type is used for the terminal block. Use the following suitable wires
for the wiring.
Terminal block socket
Phoenix Contact model No.
No. of pins
Part number
18 pins
MC1,5/18-ST-3,5BK
Suitable wires (strand wire)
No. of wires
Size
1
AWG#28 to 16
2
AWG#28 to 20
Pole terminals with compatible insulation sleeve
If a pole terminal is being used, the following models (made by Phoenix Contact) should be
used.
Cross-
Manufacturer
sectional
area
0.25 mm
0.34 mm
0.50 mm
Phoenix Contact
0.75 mm
1.00 mm
0.5 mm
Pressure welding tool for pole terminals
Phoenix Contact model No.
Manufacturer
Part number
Phoenix Contact
CRIMPFOX 6
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Product No.
1840528
Nominal cross-
sectional area
0.08 mm
0.08 mm
Phoenix Contact Par No.
Size
With insulating sleeve
2
AWG#24
AI 0,25-6 BU
2
AWG#22
AI 0,34-6TQ
2
AWG#20
AI 0,5-6 WH
2
AWG#18
AI 0,75-6 GY
2
AWG#16
-
2
×2
AWG#20×2
AI-TWIN 2X 0,5-8 WH
Product No.
1212034
2
2
to 1.25 mm
2
2
to 0.5 mm
Without insulating sleeve
A 0,25-7
A 0,34-7
A 0,5-6
A 0,75-6
A 1-6
-