OPERATION FREQUENCY WHEN POWER SUPPLY IS TURNED
ON (Parameter d51)
In the case of the door control, the operation frequency after the power supply
is turned ON can be set.
After the power supply is turned ON, the run signal changes to ON, the inverter
start operating with the operation frequency when the power supply is ON.
When the arrival signal is detected, the inverter returns to the normal operation
mode.
Data setting range (Hz)
Note) When the value is set to "0", the operation frequency is the operation mode of the
door position data when the power supply is turned OFF.

DOOR WIDTH MEASUREMENT FREQUENCY (Parameter d52)

Used to set the door width measurement frequency.
(See page 76, supplementary explaination of the door width measurement)
Data setting range (Hz)
Note ) Always use the door width measurement frequency at low speed.
When measuring the door width according to the factory setting dara (2Hz),
please increase the frequency, if the door does not activate or operate slowly.

D Region Password (Parameter d53)

A password can be set to prevent unintentional changes to the parameter data
after it has been set.
Set the password for d region parameter with Parameter d53.
d region password setting 000 1 to 999 ("000" indicates that there is no password.)
Procedures for changing parameter data after setting password
Example when password is set to "777" for parameter d53.
Press the STOP button to stop the inverter.
When the MODE button is pressed six times, the
password input display (d.PS) will appear, and the
main display will flicker.
Press the
previously set password. (The main display will flicker.)
The parameter No. will appear when the SET button is pressed.
( Example: When the previous parameter No. is "P01".)
After this step, the data is changed with the normal changing procedures.
Note) After the password is set, the "function setting mode" cannot be called without
inputting the password.(Write down the password so that you do not forget it.)
72
0
0.5 to 250 ("0" is set to no function setting.)
0.5 to 250
(up) and
(down) buttons to display the
Data setting value
Main display
d.