RIDE-THROUGH RESTART(Parameter P24)
! Caution
Depending on the restart setting after an instantaneous power failure, the
inverter may automatically start(restart) if the power is restored after a power
failure. Keep out of the machine.
(Operate the inverter after ensuring personal safety. Failure to do so could
lead to injury.)
Used to select the restart mode after an instantaneous power failure occurs,
according to the load conditions and system. A wait timer function is built-in.
Inverter operation in regard to instantaneous power failure time
Data
setting
Min. 15ms or
value
less (Note 1)
0
Operation
1
continues
2

[When voltage drop time is more than 15ms but less than 100ms]

Data setting value
"0"(No restart after
an instantaneous
failure)
Data setting value
"1"(0Hz restart)
Data setting value
"2"(continue to restart)
50
Exceeding min.15ms
(Note 1)
The LU trips, and the inverter operates according to the start
mode setting.
"LU" will be displayed, and a fault warning signal will be output.
Restart from 0Hz after the wait time has elapsed.
"LU" will be displayed, but a fault warning signal
will not be output.
After the wait time has elapsed, the inverter restarts
at the frequency applied before the ride-through
restart occurred.
"LU" will be displayed, but a fault warning signal
will not be output.
Power
supply
0
Output
frequency
0
Output
frequency
0
Output
frequency
0
Min. 100ms
(Note 2)
Voltage drop time
LU level
Operates according to the start mode
LU
setting details
trip
Wait time
LU
(parameter P25)
trip
LU
trip
Exceeding min.
100ms (Note 2)
Operation
takes place
according to
the details
set in the
start mode.
Current limit function