Parameter P80:
Function select of safety sensor signal in control input terminal No.5 may be carried out.
Setting data
value
When safety sensor signal is ON, fault OPEN operation is
0
carried out.
When CLOSE command signal is ON, and safety sensor
1
signal is ON, fault CLOSE operation iscarriedout.
2
Operation is carried out as fault CLOSE command signal.
When data value is set to be 0
After safety sensor signal is ON, OPEN operation is forced to becarried out by
the door in virtue of obstacle detect function. Response time of safety sensor
signal may be set with Parameter P44.
When data value is set to be 1
In the state that CLOSE command signal is ON, after safety sensor signal is ON,
fault CLOSE operation is carried out by the door. In case of no CLOSE command
signal, no fault CLOSE operation will be carried out even if safety sensor signal is ON.
When data value is set to be 2
Control input terminal No.5 serves as fault CLOSE command signal.
When fault CLOSE command signal is ON, fault CLOSE operation will be carried
out. Only with fault CLOSE command, fault CLOSE operation will be carried out.
Priority order of the three run commands (OPEN command, CLOSE command
and fault CLOSE command) is as follows. When all of the three signals are ON
simultaneously, note that operation will becarried out according to the following
priority order.
(Note) When fault CLOSE operation is being carried out in CLOSE operation
region, and fault CLOSE command signal is OFF (OPEN command and CLOSE
command are both OFF), note that operation will be different due to setting value
of Parameter P75 ( stop select in OPEN/CLOSE operation).

About fault CLOSE operation

In the event that signal input in control input terminal No.5 (parameter 80 is 1 or 2 )
is ON, fault CLOSE operation is carried out according to frequency and acceleration /
deceleration time in fault CLOSE operation.
Hold operation is identical to CLOSE hold operation.
In fault CLOSE operation, OPEN operation is carried out when OPEN command is ON.
In fault CLOSE operation, obstacle detect (time, slip and current) is still effective.
Obstacle detect conducted in fault CLOSE operation, its setting value is that of
parameter 81: forced OPEN operation judgment time in fault CLOSEoperation.
When RY1 2 3function select (P48 P50
to be ON in fault CLOSE operation.
Safety sensor function select
OPEN
command
Functions
fault
CLOSE
command
6 r6, , obstacle detect signal is set
CLOSE
command
65