Technical data

4.3.6.1

Power Modules Blocksize, 1-ph. AC

Table 4- 23
Technical data PM340, FSA (1-phase AC)
Line voltage 1-phase 200 ... 240 VAC ± 10%
PM340
PM340 with integrated line filter
Output current
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
Peak current l
max
Unit rating based on I
n 1)
Rated pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 VDC supply
for the Control Unit
Rated input current
2)
with/without integrated line reactor
Class J UL fuses
Rated current
Short-circuit current rating
SCCR
Circuit-breaker type designation
EN 60947
Rated current
Circuit-breaker type designation
UL489 / CSA C22.2 No. 5-02
Rated current
Rated short-circuit current SCCR
Resistance value of the external
braking resistor
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
DANGER
6SL3210– 1SB11-0UA0
6SL3210– 1SB11-0AA0
A
A
A
s6
A
kW
kHz
kW
m
/s
3
dB
A
A
A
kA
A
A
kA
Ω
0,9
0,8
1,4
2,0
0,12
4
0,06
0,005
< 45
1,0
1,4 / 2,2
6
65
5SJ4206-7HG41
6
5SJ4206-7HG41
6
14
> 180
4.3 Power Modules Blocksize (PM340)
1SB12-3UA0
1SB12-3AA0
2,3
2,0
3,3
4,6
0,37
4
0,075
0,005
< 45
1,0
4 / 6
10
65
5SJ4210-7HG41
10
5SJ4210-7HG41
10
14
> 180
Power Modules
1SB14-0UA0
1SB14-0AA0
3,9
3,4
5,5
7,8
0,75
4
0,11
0,005
< 45
1,0
6,5 / 10
15
65
5SJ4216-7HG41
16
5SJ4216-7HG41
16
14
> 180
145