Service and maintenance
11.3 Service and maintenance for Chassis format components
Installation
To reinstall, perform the above steps in reverse order.
Note
Connecting fiber-optic cables
The fiber-optic cable plugs must be re-inserted at their original slot. Fiber-optic cables and
sockets are accordingly labeled for correct assignment (U11, U21, U31).
NOTICE
Material damage caused by loose power connections
Insufficient tightening torques can result in faulty electrical connections. This can cause fire
damage or functional faults.
• Tighten all power connections with the specified tightening torques, e.g. line supply
Note
Connection clip to the interference-suppression capacitor
The connection clip to the interference-suppression capacitor is mounted on the spare power
block together with a yellow warning label.
Please note the information in Chapter "Electrical connection" of the corresponding device.
468
connection, motor connection.
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4