4.3 Power Modules Blocksize (PM340)
Line voltage 1-phase 200 ... 240 VAC ± 10%
PM340
PM340 with integrated line filter
Max. cable length
to braking resistor
Line supply connectionL, N
Motor connection U2, V2, W2
DC-link connection, connection for
braking resistorDCP/R1, DCN, R2
PE connection
Max. motor cable length
(without external options)
Degree of protection
Weight
Rated output of a typical standard induction motor at 230 V.
1)
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
2)
(based on I
) for a line impedance corresponding to u
rated
Max. motor cable length 15 m (shielded) for PM340 Power Modules with integrated line filter to maintain the limit values
3)
of EN 61800-3 Category C2.
146
6SL3210– 1SB11-0UA0
6SL3210– 1SB11-0AA0
m
15
Screw terminals for cable cross-sections 1.0 to 2.5 mm
At the housing with M4 screw
m
50 (shielded)
3)
75 (unshielded)
IP20 or IPXXB
kg
1,2
1SB12-3UA0
1SB12-3AA0
15
1,3
= 1%.
k
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
1SB14-0UA0
1SB14-0AA0
15
2
1,3