Cabinet design and EMC for components, Blocksize format
10.9 Information on control cabinet cooling
10.9.3.4
Power loss for Power Modules
Table 10- 23 Overview of power loss during rated operation for Power Modules
Rated output current I
rated
based on I
rated
PM240-2 Blocksize
7.5 A / 0.55 kW
9.6 A / 0.75 kW
13.5 A / 1.1 kW
1801 A / 1.5 kW
24.0 A / 2.2 kW
35.9 A / 3.0 kW
43.0 A / 4.0 kW
29.0 A / 5.5 kW
37.0 A / 7.5 kW
2.3 A / 0.55 kW
2.9 A / 0.75 kW
4.1 A / 1.1 kW
5.5 A / 1.5 kW
7.7 A / 2.2 kW
10.1 A / 3.0 kW
13.3 A / 4.0 kW
17.2 A / 5.5 kW
22.2 A / 7.5 kW
32.6 A / 11.0 kW
39.9 A / 15.0 kW
PM240-2 Blocksize Push Through
9.6 A / 0.75 kW
24.0 A / 2.2 kW
43.0 A / 4.0 kW
10.1 A / 3.0 kW
22.2 A / 7.5 kW
39.9 A / 15.0 kW
450
/Unit rating
Frame size
FSA
FSA
FSB
FSB
FSB
FSC
FSC
FSC
FSC
FSA
FSA
FSA
FSA
FSA
FSA
FSB
FSB
FSB
FSC
FSC
FSA
FSB
FSC
FSA
FSB
FSC
Line voltage
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
3-phase 200 ... 240 VAC
3-phase 200 ... 240 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
1-phase/3-phase 200 ...
240 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
3-phase 380 ... 480 VAC
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Unit
Power loss
kW
0,04
kW
0,04
kW
0,05
kW
0,07
kW
0,12
kW
0,14
kW
0,18
kW
0,2
kW
0,26
kW
0,04
kW
0,04
kW
0,04
kW
0,07
kW
0,1
kW
0,12
kW
0,11
kW
0,15
kW
0,2
kW
0,3
kW
0,37
kW
0,04
kW
0,12
kW
0,18
kW
0,12
kW
0,2
kW
0,37
AC Drive