Behavior Of The Leds In The Operating State - Siemens S120 Manual

Hide thumbs Also See for S120:
Table of Contents

Advertisement

Control Units, Control Unit Adapters and operating components
7.4 Control Unit CU310-2 DP (PROFIBUS)
7.4.4.3

Behavior of the LEDs in the operating state

Table 7- 39
Description of the LEDs during operation of the CU310-2 DP
LED
Color
RDY
-
(READY)
Green
Red
Red/green
Orange
Green/oran
ge
or
red/orange
COM
-
Green
Red
312
State
Description / cause
OFF
The electronics power supply is missing or outside
the permissible tolerance range.
Continuous light
The unit is ready for operation.
Cyclic DRIVE-CLiQ communication is in progress.
Flashing light
Commissioning/reset
0.5 Hz
Flashing light 2
Writing to the memory card.
Hz
Flashing light
General fault
2 Hz
Flashing light
The control unit is ready for operation, but there
0.5 Hz
are no software licenses.
Flashing light
Updating the firmware of the DRIVE-CLiQ
0.5 Hz
components.
Flashing light
DRIVE-CLiQ component firmware update
2 Hz
completed. Waiting for POWER ON of the
corresponding components.
Flashing light
Recognition of the component via LED is activated
2 Hz
(see SINAMICS S120/S150 List Manual).
Note:
Both possibilities depend on the status of the LED
when activating.
OFF
Cyclic communication is not (yet) running.
Note:
The PROFIdrive is ready for communication when
the Control Unit is ready for operation (see LED:
RDY).
Continuous light
Cyclic communication is taking place.
Flashing light
Cyclic communication is not fully established yet.
0.5 Hz
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller is not sending
a GC (Global Control) or is sending a defective
GC.
Flashing light
The PROFIBUS master is sending a faulty
0.5 Hz
parameter assignment or the configuration file is
corrupted.
Flashing light
Cyclic bus communication has been interrupted or
2 Hz
could not be established.
Remedy
Check the power
supply
-
-
-
Check parameter
assignment/configurati
on
Install the missing
licenses.
-
Switch on the
component.
-
-
-
-
Modify the
configuration between
master/controller and
control unit.
Rectify the fault in bus
communication.
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
AC Drive