Characteristics - Siemens S120 Manual

Hide thumbs Also See for S120:
Table of Contents

Advertisement

Power Modules
4.4 Power Modules Chassis
4.4.6.1

Characteristics

Overload capability
The Power Modules are equipped with an overload reserve, e.g. to handle breakaway
torques.
In drives with overload requirements, the appropriate base load current must, therefore, be
used as a basis for the required load.
The overload data is valid under the precondition that the Power Module is operated with its
base load current before and after the overload occurs (a load duration of 300 s is used as a
basis here).
Low overload
The base load current for low overload I
150% for 10 s with a load duty duration of 300 s.
Figure 4-64
174
Characteristic: Low overload
is based on a load duty cycle of 110% for 60 s or
L
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
AC Drive

Advertisement

Table of Contents
loading

Table of Contents