Siemens S120 Manual page 152

Hide thumbs Also See for S120:
Table of Contents

Advertisement

Power Modules
4.3 Power Modules Blocksize (PM340)
Table 4- 28
Technical data PM340, FSE and FSF (3 AC 380 V to 480 V ±10 %)
PM340
PM340 with integrated line
filter
Frame size
Output current
Rated current I
n
Base-load current I
H
for S6 operation (40 %) l
Peak current l
max
Type rating
1)
on basis of I
n
on basis of I
H
Rated pulse frequency
Power loss
Cooling air requirement
Sound pressure level L
pA
(1 m)
24 V DC supply
for the Control Unit
Rated input current
2)
with/without integrated line
reactor
UL fuses
Class J
Rated current
Short-circuit current rating
SCCR
NH fuses
IEC 60947
Rated current
Circuit breaker type
designation
IEC 60947
Rated current
Resistance value
of the external braking
resistor
Max. cable length
to braking resistor
Line supply connection
L1, L2, L3
Motor connection
U2, V2, W2
DC link connection,
connection for braking
resistor
DCP/R1, DCN, R2
152
6SL3210-
1SE27-5UA0
6SL3210-
1SE27-5AA0
FSE
A
75
A
65
A
98
s6
A
124
kW
37
kW
30
kHz
4
kW
0,99
m
/s
0,022
3
dB
< 60
A
1,0
A
78 / 88
3NE1021-0
A
100
kA
65
3NA3830
A
100
3VL1712-
1DD33-0AA0
A
100 ... 125
Ω
> 15
m
15
Stud M6,
connectable cable cross-
sections 10 ... 50 mm
1SE31-0UA0
1SE31-1UA0
1SE31-0AA0
1SE31-1AA0
FSE
FSF
90
110
80
95
117
143
150
180
45
55
37
45
4
4
1,21
1,42
0,039
0,094
62
< 60
1,0
1,0
94 / 105
115 / 129
3NE1022-0
3NE1224-0
125
150
65
65
3NA3832
3NA3836
125
160
3VL1716-
3VL3720-
1DD33-0AA0
1DC36-0AA0
125 ... 160
160 ... 200
> 8,2
Stud M8,
max. connectable cable cross-section 120
mm
2
2
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
1SE31-5UA0
1SE31-8UA0
1SE31-5AA0
1SE31-8AA0
FSF
FSF
145
178
115
155
188
231
220
290
75
90
55
75
4
4
1,93
2,31
0,094
0,117
< 60
65
1,0
1,0
151 / 168
186 / 204
3NE1225-0
3NE1227-0
200
250
65
65
3NA3140
3NA3144
200
250
3VL3720-
3VL3725-
1DC36-0AA0
1DC36-0AA0
160 ... 200
200 ... 250
AC Drive

Advertisement

Table of Contents
loading

Table of Contents