Figure 11-15 Forming circuit for 1-ph AC Power Modules with resistors
Procedure
● Make sure that the device does not receive a power-on command (e.g. from the keyboard
● Connect the forming circuit.
● While forming, the incandescent lamps must become less bright or go completely dark. If
● To form using resistors, the modules must remain in the circuit for approx. 1 h. The
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
or terminal block).
the incandescent lamps continue to be brightly lit, a fault has occurred in the drive unit or
in the wiring.
resistors will become very hot if there is a fault in the unit (surface temperature > 80 °C).
Service and maintenance
11.4 Forming the DC link capacitors