The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130-, PTC- or PT100 probe in the stator windings.
Note
A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and -
X9:7.
4.4.3.6

X42 terminal strip

Table 4- 32
Terminal block -X42:
Terminal
1
2
3
4
Max. connectable cross-section: 2.5 mm
Note
When delivered, terminals 1 and 4 are provided with a connecting cable to supply a CU310-2
DP or CU310-2 PN Control Unit.
Note
Connection options for the X42 terminal strip
The terminal block is not intended for free 24 V DC availability (for example for supplying
further line-side components), as the voltage supply of the Control Interface Module could
also be overloaded and operating capability could thus be compromised.
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Function
Technical data
P24L
Voltage supply for Control Unit, Sensor Module, and Terminal Module
(18 to 28.8 V)
Maximum load current: 3 A
M
2
Power Modules
4.4 Power Modules Chassis
165