10.6.3
Current-carrying capacity and derating factors for power cables and signal
cables
The current-carrying capacity of PVC/PUR-insulated copper cables is specified for routing
types B1, B2 and C under continuous operating conditions in the table with reference to an
ambient air temperature of 40 °C. For other ambient temperatures, the values must be
corrected by the factors listed in the "Derating factors for deviating ambient temperatures"
table.
Table 10- 12 Current carrying capacity according to EN 60204-1 for 40 °C ambient temperature
Cross-section
mm
Electronics
0,20
0,50
0,75
Power
0,75
1,00
1,50
2,50
4
6
10
16
25
35
50
70
95
120
Table 10- 13 Current carrying capacity according to IEC 60364-5-52 for 40 °C ambient temperature
Cross-section
Power
150
185
> 185
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Current carrying capacity, effective; AC 50/60 Hz or DC
For routing type
B1
2
A
8,6
10,3
13,5
18,3
24
31
44
59
77
96
117
149
180
208
Current carrying capacity, effective; AC 50/60 Hz or DC
For routing type
Values must be taken
from the standard
Cabinet design and EMC for components, Blocksize format
B2
A
4,3
7,5
9
8,5
10,1
13,1
17,4
23
30
40
54
70
86
103
130
165
179
10.6 Connection Methods
C
A
4,4
7,5
9,5
9,8
11,7
15,2
21
28
36
50
66
84
104
125
160
194
225
344
392
435