5.2.1.6

Braking resistor connection X1

Table 5- 8
Braking resistor connection
Terminal
R1
R2
Max. cross-section that can be connected: 50 mm
5.2.1.7

X21 digital inputs/outputs

Table 5- 9
Terminal block X21
Terminal
1
2
3
4
5
6
Max. connectable cross-section 1.5 mm
DI: Digital input; DO: Digital output
1)
Note
When the Braking Module is in the installed state, the individual terminals on its X21 terminal
block are positioned as follows: terminal "1" is at the rear, terminal "6" at the front.
Note
Applying a high signal to terminal X21.3 inhibits the Braking Module. On a falling edge,
pending error signals are acknowledged.
Note
You will find setting instructions for wiring the signals in the SINAMICS S120 Function
Manual.
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Designation
Braking resistor connection R+
Break resistor connection R-
2
Designation
Technical data
1)
Shield
Shield connection for terminal 2 ... 6
0 V
Low signal level: -3 ... 5 V
High signal level: 15 ... 30 V
DI inhibit input
Current consumption: 2 ... 15 mA
0 V
Voltage: 24 V DC
Load current: 0.5 ... 0.6 A
DO fault output
+24 V
Voltage: 18 ... 30 V

 T ypical current consumption (own current consumption): 10 mA at 24 V
DC
2
DC link components
5.2 Chassis
197