4.4.3.3

Terminal Block X9

Table 4- 29
Terminal block X9
Terminal
1
2
3
4
5
6
7
8
Note
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.
Note
If the "Safe Torque Off" function is selected, 24 V DC must be applied to terminal -X9:7 and
terminal -X9:8 must be grounded. Upon removal, pulse inhibit is activated.
4.4.3.4

DCPS, DCNS connection for a dv/dt filter

Table 4- 30
Frame size
FX
GX
The connecting cable is fed-out downwards through the Power Module.
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Signal name
P24V
M
Reserved, do not use
Reserved, do not use
Main contactor
Main contactor
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
DCPS, DCNS
Cross-section that can be connected
1 x 35 mm²
1 x 70 mm²
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max 1.4 A
240 V AC/ max. 8 A
30 V DC/ max. 1 A
Supply voltage: 24 V DC (20.8 V ... 28.8 V)
Current consumption: 10 mA
Signal propagation delays:
L -> H: 100 µs
H->L: 1000 µs
The pulse disable function is only available when Safety
Integrated Basic Functions are enabled.
Terminal screw
M8
M8
Power Modules
4.4 Power Modules Chassis
163