X11 Interface To The Control Interface Module; X12 230 V Ac Power Supply - Siemens S120 Manual

Hide thumbs Also See for S120:
Table of Contents

Advertisement

8.3.3.2

X11 interface to the Control Interface Module

Table 8- 25
X11 interface to the Control Interface Module
Terminal
Signal
X11.1
BR+
X11.2
BR-
X11.3
FB+
X11.4
FB-
X11.5
P24
X11.6
M
Max. connectable cross-section: 2.5 mm
Fire hazard due to overheating when permissible cable lengths are exceeded
Excessively long power cables can cause overheating of components with resulting fire and
smoke development.
• The maximum permissible cable length of 10 m between the 230 V AC Safe Brake
8.3.3.3

X12 230 V AC power supply

Table 8- 26
X12 230 V AC power supply
Terminal
Signal
X12.1
L
X12.2
N
Max. connectable cross-section: 2.5 mm
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Supplementary system components and encoder system integration
Description
Control channel 1
Control channel 2
Relay feedback signal
Ground of the relay feedback signal
P24 of the auxiliary voltage to supply the
feedback signal
Ground of the auxiliary voltage
2
WARNING
Adapter and the Control Interface module must not be exceeded.
Use the cable harness (length: 4 m) order no. 6SL3060-4DX04-0AA0.
Technical data
Supply voltage: AC 230 V
Current consumption: 2 A
2
8.3 Safe Brake Adapter optional module
Technical data
Connection to Control Interface Board, X46.1
Connection to Control Interface Board, X46.2
Connection to Control Interface Board, X46.3
Connection to Control Interface Board, X46.4
Connection to Control Interface Board, X42.2
Connection to Control Interface Board, X42.3
387

Advertisement

Table of Contents
loading

Table of Contents