Mains connection and line-side power components
3.8 Line reactors
3.8.4

Mounting

Blocksize line reactors for PM240-2
The line reactors for Power Modules PM240-2 of frame sizes FSA to FSC are designed for
installation in a cabinet. The line reactor is installed on the mounting surface next to the
Power Module. The line reactor is connected to the line supply through terminals.
Table 3- 12
Connecting the line reactor for the PM240-2 on the mounting surface
Frame size
FSA
FSB
FSC
64
Fastening
4 x M5 screws
4 x M5 nuts
4 x M5 washers
4 x M6 screws
4 x M6 nuts
4 x M6 washers
Tightening torque
6 Nm
10 Nm
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4