6 Enter interface configuration mode for the CNA-facing ports and
configure the DCBx port role as auto-downstream. This step automatically
enables PFC on the ports.
console(config)#interface te1/0/1-3
console(config-if)#lldp dcbx port-role auto-down
console(config-if#exit
7 Enter Interface Configuration mode for the ports connect to an FCF to
configure the DCBx port role as auto-upstream.
console(config)#interface te1/0/16-17
console(config-if)#lldp dcbx port-role auto-up
8 Set the FIP snooping port mode as
connected to a Fibre Channel forwarder.
console(config-if)#fip-snooping port-mode fcf
console(config-if)#exit
9 Optionally, use the FIP snooping show commands to verify the
configuration, view FIP snooping sessions, and view information about the
ports that are connected to end nodes or FCFs.
Enhanced Transmission Selection Operation with
DCBx
PowerConnect M8024-k switches can act as a proxy for ETS information via
the auto configuration mechanism. ETS information received from the
configuration source is transmitted via DCBX to the other auto configuration
peers.
While M8024-k switches are not equipped with a hierarchical scheduler, they
do support the following ETS capabilities:
Both lossy and lossless service using PFC (may be configured via DCBX).
Sharing of unused bandwidth with lower priority traffic classes (default
behavior). Sharing of bandwidth is disabled when the minimum
bandwidth assignments sum to 100%.
WRR or strict-priority scheduling (configured manually).
fcf to indicate that these ports are
Configuring Data Center Bridging Features