Raising And Lowering Frequency References Using Contact Signals (Up/Down) - YASKAWA varispeed G7 CIMR-G7B series Instruction Manual

General purpose inverter (advanced vector control)
Table of Contents

Advertisement

Application Precautions
When d4-01 is set to 1, the output frequency on hold is stored even after the power supply is turned OFF. If
performing operations using this frequency after the Inverter has also been turned OFF, input the Run
Command with the Acceleration/Deceleration Ramp Hold turned ON.
When d4-01 is set to 0 and a Run Command is input while the Acceleration/Deceleration Ramp Hold is
turned ON, the output frequency will be set to zero.
If you input an Acceleration/Deceleration Ramp Hold command by error when decelerating during posi-
tioning, deceleration may be canceled.
Raising and Lowering Frequency References Using Contact Signals (UP/
DOWN)
The UP and DOWN commands raise and lower Inverter frequency references by turning ON and OFF a multi-
function contact input terminal S3 to S7.
To use this function, set one of the constants H1-01 to H1-10 (multi-function contact input terminal S3 to S12
function selection) to 10 (UP command) and 11 (DOWN command). Be sure to allocate two terminals so that
the UP and DOWN commands can be used as a pair.
The output frequency depends on the acceleration and deceleration time. Be sure to set b1-02 (Run Command
selection) to 1 (Control circuit terminal).
Related Constants
Name
Con-
stant
Display
Number
Frequency ref-
Set the output frequency upper
erence upper
d2-01
limit as a percent, taking the max.
limit
output frequency to be 100%.
频率指令上限
Frequency ref-
Sets the output frequency lower
erence lower
d2-02
limit as a percentage of the maxi-
limit
mum output frequency.
频率指令下限
Master speed
Set the master speed reference
reference lower
lower limit as a percent, taking
d2-03
limit
the max. output frequency to be
100%.
主速指令下限
Precautions
When setting and using UP and DOWN commands, observe the following precautions.
Setting Precautions
If multi-function input terminals S3 to S12 are set as follows, operation error OPE03 (Invalid multi-function
input selection) will occur:
Only either the UP command or DOWN command has been set.
UP/DOWN commands and Acceleration/Deceleration Ramp Hold have been allocated at the same time.
Setting
Factory
Description
Range
0.0 to
110.0
0.0 to
110.0
0.0 to
110.0
Input Terminal Functions
Control Methods
Change
Open
during
V/f
Loop
Setting
Opera-
V/f
with
Vector
tion
PG
1
100.0
No
A
A
A
%
0.0%
No
A
A
A
0.0%
No
A
A
A
MEMO
Open
BUS
Flux
Loop
Regis-
Vec-
Vector
ter
tor
2
A
A
289H
A
A
28AH
A
A
293H
79
6-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents