Switch
o1-03 F3-01
S1
12 bits
2 to 39
-
16 bits
X0040
-
12 bits
to
X9999
(X = 0
-
16 bits
to 3)
X1000
(X = 0
-
16 bits
to 3)
DI-08 Reference Ranges
When using the DI-08, the following ranges can be set depending on the settings of the constants.
F3-01
Reference Input Mode
0
2-digit BCD with sign, 1%
1
2-digit BCD with sign, 0.1%
2
2-digit BCD with sign, 0.01%
3
2-digit BCD with sign, 1 Hz
4
2-digit BCD with sign, 0.1 Hz
5
2-digit BCD with sign, 0.01 Hz
6
7
8-bit binary with sign, 100%/255
Reference Input Mode
3-digit BCD with sign, 1 rpm
4-digit BCD with sign, 1 rpm
3-digit BCD with sign, 100%/(1- to 4-
digit setting of o1-03)
4-digit BCD with sign, 100%/(1- to 4-
digit setting of o1-03)
4-digit BCD with sign, 100%/10000
Reference Setting Range
-110 to 110%
-15.9 to 15.9%
-1.59 to 1.59%
-159 to 159 Hz
-15.9 to 15.9 Hz
-1.59 to 1.59 Hz
-
-255 to 255
U1-01 Monitor Unit
Reference Setting
Range
o1-03 = 0
-1599 to 1599 rpm
-15999 to 15999 rpm
-1599 to 1599
5th digit of o1-03 set-
ting:
-9999 to 9999
X = 0, unit: 1
(when o1-03 = 9999)
X = 1, unit: 0.1
X = 2, unit: 0.01
X = 3, unit: 0.001
-1000 to 1000
U1-01 Monitor Unit
o1-03 = 0
0.01 Hz
Options
o1-03 = 1
1 rpm
1 rpm
o1-03 = 1
0.01%
169
6-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents