C: Autotuning Constants

The following settings are made with the autotuning constants (C constants): Acceleration/deceleration times,
s-curve characteristics, slip compensation, torque compensation, speed control, and carrier frequency func-
tions.
Acceleration/Deceleration: C1
User constants for acceleration and deceleration times are shown in the following table.
Name
Con-
stant
Display
Number
Accelera-
Sets the acceleration time to
tion time 1
accelerate from 0 to the maxi-
C1-01
mum output frequency, in 1-
加速时间 1
second units.
Decelera-
Sets the deceleration time to
tion time 1
decelerate from the maximum
C1-02
output frequency to 0, in 1-
减速时间 1
second units.
Accelera-
The acceleration time when
tion time 2
the multi-function input
C1-03
"accel/decel time 1" is set to
加速时间 2
ON.
Decelera-
The deceleration time when
tion time 2
the multi-function input
C1-04
"accel/decel time 1" is set to
减速时间 2
ON.
Accelera-
The acceleration time when
tion time 3
the multi-function input
C1-05
"accel/decel time 2" is set to
加速时间 3
ON.
Decelera-
The deceleration time when
tion time 3
the multi-function input
C1-06
"accel/decel time 2" is set to
减速时间 3
ON.
Accelera-
The acceleration time when
tion time 4
the multi-function input
C1-07
"accel/decel time 1" and
"accel/decel time 2" are set to
加速时间 4
ON.
Decelera-
The deceleration time when
tion time 4
the multi-function input
C1-08
"accel/decel time 1" and
"accel/decel time 2" are set to
减速时间 4
ON.
Emergency
The deceleration time when
stop time
the multi-function input
"Emergency (fast) stop" is set
C1-09
to ON.
This function can be used as a
紧急停止时间
stopping method when a fault
has been detected.
Setting
Factory
Description
Range
Setting
0.0 to
10.0 s
6000.0
*
User Constant Tables
Control Methods
Change
Open
during
V/f
Loop
Flux
Opera-
V/f
with
Vec-
Vec-
tion
PG
tor
tor
1
Yes
Q
Q
Q
Q
Yes
Q
Q
Q
Q
Yes
A
A
A
A
Yes
A
A
A
A
No
A
A
A
A
No
A
A
A
A
No
A
A
A
A
No
A
A
A
A
No
A
A
A
A
MEMO-
Open
BUS
Loop
Page
Regis-
Vec-
ter
tor
2
4-5
Q
200H
4-21
6-18
4-5
Q
201H
4-21
6-18
4-21
A
202H
6-18
4-21
A
203H
6-18
4-21
A
204H
6-18
4-21
A
205H
6-18
4-21
A
206H
6-18
4-21
A
207H
6-18
4-21
A
208H
6-17
21
5-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents